Abstract
Recent ejector studies have focused on the design and performance of the two-phase ejector and its effect on the performance of the ejector cycle. However, recent experimental work has shown that the effect of evaporator design on ejector cycle performance can also be quite significant. In this paper, a numerical model of a microchannel air-to-refrigerant evaporator, capable of accounting for heat transfer and pressure drop effects, is used to investigate the effect that different evaporator dimensions have on the performance of ejector cycles. Two ejector cycles are compared: The standard ejector cycle, in which the ejector is used to directly lift compressor suction pressure, and the ejector recirculation cycle, in which the ejector overfeeds the evaporator but does not directly lift compressor suction pressure. The effects of microchannel port hydraulic diameter, number of evaporator passes, and liquid feed rate are investigated. The analysis is performed with refrigerants R410A and CO2.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.