Abstract

In order to minimize the hot air recirculation (HAR) to ensure normal operation of the air-cooled condensers (ACC) system, the hot air recirculation phenomenon and its dependence on ambient winds are numerically simulated by using the computational fluid dynamics code, FLUENT. Under the constant ambient temperature, the effects of different wind speed and wind direction on the HAR are qualitatively considered by applying the concept of the hot recirculation rate (HRR). The mechanism of occurrence of hot air recirculation are presented and analyzed. It was found that when considering about the existing and normally operating power plants, the HAR is more sensitive to wind direction and wind speed. Based on the above results, two improved measures increasing the wind-wall height and accelerating the rotational speed of the fans near the edge of the ACC platform are developed to effectively reduce the hot air recirculation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.