Abstract
Tower surge responses are computed by the numerical electromagnetic code. The code used in this paper is not the one based on the circuit theory such as the Electromagnetic Transients Program (EMTP), but the one that solves the electric field equations directly by the moment method. The accuracy of this method is shown to be satisfactory by comparison with experimental results that were carried out on an actual UHV tower as well as reduced-scale models. And then by using this method, the influences of tower elements such as slant elements, horizontal elements and crossarms on the tower surge characteristics are investigated. In addition, the surge impedance of a full-sized tower hit directly by a lightning stroke is discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.