Abstract
This paper numerically studies the heat transfer in heat sinks with micro-pin-fins. Commercial software, ICEPAK, was used to explore the effect of micro-pin-fin array design on the flow rate and heat transfer characteristics of liquid cooling heat sink. The parameters include the diameter of pin fin, the gap between the pin fins, and the relative position between the pin fins. The diameters of the pin fin are 0.5mm, 0.6mm, and 0.7mm, respectively. The gap between the pin fins are 0.2mm, 0.25mm, 0.3mm, 0.4mm, and 0.5mm, respectively. Three types of fin array arrangements are set with different longitudinal spacing and transverse spacing. The driving force of the working fluid is the pressure head with 500, 1500, and 3000 Pa, respectively. Results show that the effective thermal resistance ranges from 0.27 to 0.55 with the power density of 300kW/m2.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.