Abstract

Preliminary field measurements have shown substantial temperature sudden-drop (ΔTsd) at bird level in the initial stage of pad cooling process in arid regions of China. Such sudden temperature fluctuation can cause thermal stress to laying hens and this problem is attracting increasing concerns. The purpose of this study was to develop a new control strategy (NCS) to avoid or minimize ΔTsd while simplifying the operational process. Theoretical calculation and field test were conducted in this study. The key ambient thermal factor affecting ΔTsd was analysed by calculating temperature drop of cooled air existing the cooling pad (ΔTd). A countermeasure was applied by controlling the wetted pad area at each startup of the water supply pump. Field test was carried out to demonstrate the application of the NCS in a poultry house. The theoretical arithmetic results showed that ambient relative humidity (RHo) was the main factor affecting ΔTd, and ΔTsd occurred when RHo ≤ 60%. Temperature fluctuation at the bird level (Tdb,b) could be controlled within 4°C when the wetted pad area increased by 25%. The NCS operated based on RHo that was divided into three regions. For RHo > 80%, the pump would not be turned on because of poor cooling effect. For 60% < RHo < 80%, no ΔTsd would occur and the pump would be controlled by “on-off” regulation. For RHo ≤ 60%, ΔTsd occurred and the pump was turned on intermittently. Then, 4-stage cooling would be applied. Results of the field test were generally consistent with the theoretical simulation with regards to alleviation of ΔTsd that was controlled within 3.5°C. Further field verification of the NCS on the flock health and production performance is warranted. Keywords: evaporative cooling, poultry housing, new control strategy, temperature fluctuation, thermal stress DOI: 10.25165/j.ijabe.20181101.2479 Citation: Hui X, Li B M, Xin H W, Zheng W C, Shi Z X, Yang X, et al. New control strategy against temperature sudden-drop in the initial stage of pad cooling process in poultry houses. Int J Agric & Biol Eng, 2018; 11(1): 66–73.

Highlights

  • Fan and pad cooling system is widely used for animal production in hot climate[1,2]

  • Temperature fluctuation at the bird level (Tdb,b) could be controlled within 4°C when the wetted pad area increased by 25%

  • The approach consists of three steps: (1) determine ΔTd –the key ambient thermal factor affecting ΔTsd under various climatic conditions, (2) find the practical measure against ΔTsd controlling the amount of wetted pad area at the start-up of the water-supply pump to avoid the maximum potential dry-bulb temperature drop and (3) incorporate the calculations into the control algorithm through programming

Read more

Summary

Introduction

Fan and pad cooling system is widely used for animal production in hot climate[1,2]. Because of its low energy cost, higher ventilation rate and good cooling efficiency[3,4,5,6,7,8], the cooling system has become a standard configuration for commercial poultry houses in hot regions[9]. For most laying-hen houses in China, operation of the pad cooling systems is decided by the farm operators according to their experiences or best judgment. The pump will be turned off when there is no need for cooling.

Objectives
Methods
Results
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.