Abstract
A neural network-based algorithm for the protection of a one-phase power transformer is considered. The neural network input is a four-dimensional vector obtained by a fast-frequency analysis of the differential current. Primary and secondary currents are measured with current transformers the saturation of which is taken into account. A set of training cases is generated with the help of the electromagnetic transients program. The neural network-based algorithm is compared with a conventional differential algorithm. It is found to be more efficient, especially in the case of saturation of the current transformers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEE Proceedings - Generation, Transmission and Distribution
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.