Abstract

A neural network-based algorithm for the protection of a one-phase power transformer is considered. The neural network input is a four-dimensional vector obtained by a fast-frequency analysis of the differential current. Primary and secondary currents are measured with current transformers the saturation of which is taken into account. A set of training cases is generated with the help of the electromagnetic transients program. The neural network-based algorithm is compared with a conventional differential algorithm. It is found to be more efficient, especially in the case of saturation of the current transformers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.