Abstract

In this study, the potential of using different natural ventilation strategies has been investigated based on a single-story, mixed-use building at Dubai. The outdoor investigations of the influence of external wind speed and pressure on the external building envelope was done using Autodesk Flow Design Software. The indoor ventilation CFD simulation (Micro-Flow analysis) was generated using IES virtual Environment software to detail the wind circulation inside the building and demonstrate the adopted strategy towards enhancing the indoor climate conditions. Cooling load calculations and energy modelling was investigated using Carrier Hourly Analysis Program (HAP) to check the energy savings due to the adopted natural ventilation strategies. It was found that the comfort conditions inside the building can be met at the 4 winter months (November-February) only by utilizing the passive cooling natural ventilation strategy without switching on the HVAC system. Hence, saving almost 21% of the annual building cooling load and almost 18% of the total annual energy used in the building.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.