Abstract

This paper describes results of a field measurement on air and thermal environment in a residential building where both radiant cooling and ventilation are realized. Combination between radiant cooling and ventilation can keep indoor CO2 concentration less than 1000 ppm and room air temperature s and MRTs 28°C or less. Radiant cooling uses less power than air conditioners with similar COP to the heat pump of panel cooling and is not remarkably affected by incoming outside air. Even if ventilation is done, external shading can realize the same SET* with higher panel temperatures than the case of non-shading.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.