Abstract

This paper proposes a multiple space vector control strategy for self-commutated power converters. The strategy makes it possible to realize a significant reduction in power losses with the lowest possible switching frequency in the steady-state, continuous operation with high speed tracking of commands in the transient state and flexible controls with the utilization of degrees of freedom in the assignment of voltage vectors to the power converters. High efficiency of the strategy is confirmed by experiments in which two pulse switching mode and the speed of response in 5(ms) with one side model of the power converter terminals of self-commutated HVDC (high voltage direct current). The continuous operation is verified by simulations in a one-line ground fault. Another simulation based on the unbalanced DC voltages shows the balance control of DC voltages to be effective in HVDC transmission with self-commutated power converters connected in series on the AC and the DC sides.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.