Abstract

This study connects several modular multilevel converters to form multi-pole voltage source converter highvoltage dc (VSC-HVDC) links which are suited for bulk power evacuation, with increased resiliency to ac and dc network faults. The proposed arrangements resemble symmetrical and asymmetrical HVDC links that can be used for bulk power transfer over long distances with reduced transmission losses, and for the creation of multi-terminal supergrids currently being promoted for transitional dc grids in Europe. The technical feasibility of the proposed systems is assessed using simulations on symmetrical and asymmetrical tri-pole VSC-HVDC links, including the case of permanent pole-to-ground dc faults.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.