Abstract

Power transformers and shunt reactors may be subjected to various dielectric stresses such as lightning and switching overvoltages. Since the exposure of equipment to overvoltages during operation and the overvoltage amplitudes are usually unknow, an on-line overvoltage transient recorder is used with the ability to sample, analyze and store transients at transformer terminals in real-time. In this paper, transient overvoltage monitoring system is presented. Overvoltages are measured on the outside measurement terminal of the shunt reactor and transformer bushing. Field experience regarding the application of monitoring system in Croatia is described including different cases of lightning and switching overvoltages. Lightning overvoltages recorded by monitoring system are correlated with data from the lightning location system (LLS). Switching overvoltages recorded on the shunt reactor are compared with numerical simulations in EMTP-RV software. Collected data about overvoltage stresses can be used as the basis for the assessment of the transformer and shunt reactor insulation condition and estimation of health index.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.