Abstract

In this paper, a model based on dynamic electric field analysis has been developed to predict the flashover voltage of the ice-covered HV insulators, under dc voltage. The potential and electric field calculation models before and after air gap breakdown are built respectively based on finite element method (FEM). The arc initiation process is determined based on the model before air gap breakdown. The critical applied voltage and leakage current to maintain an arc with certain length are obtained based on the electric field calculation model after air gap breakdown and the U-I characteristic of the arc. Moreover, the improved Hampton criterion has been employed to determine the critical flashover of the ice-covered insulator. The results obtained from the dynamic electric field analysis model have been compared with other mathematical and experimental results of other researchers and got a great agreement.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.