Abstract

We propose two schemes for identifying the parameters of models for predicting temperatures in multiple zones of office buildings. Real environments are considered for model predictive control (MPC) used to energy-efficiently operate heating, ventilation, and air conditioning (HVAC) systems. In the first part of this paper, we describe a system model of an HVAC system and the conditions of real office buildings in terms of how to estimate internal heat gain (IHG) and reduce the negative effects of uncertainties, including measurement bias. The following part shows the two schemes for solving these challenges with the key idea that typical patterns of IHG and the degree of influence of uncertainties are known when focusing on office buildings. Furthermore, we evaluated the error in predicting temperature with data measured from a real office building. We achieved a mean absolute error (MAE) of 0.36-0.37°C for 1-day ahead prediction and improved the standard deviation of MAE (27.0%), which was used as robustness measure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.