Abstract

Noise is radiated directly from the vibrating structure as structureborne noise. A structureborne noise case in a domestic building is described in this paper. The pipes were installed and mounted vertically with little or no insulation between the pipes and the walls. The result was that, every time a toilet was flushed or fresh water was used in one of the units in the building, the water flow and pump noise was heard clearly in the unit directly above the pump room. The family in the unit was very annoyed with the noise, especially in the middle of the night. The measured noise level inside the unit was found to exceed the statutory requirement of 45 dBA (Leq. 30 min) in the night time period (23:00–07:00 h). The solution to this problem was to isolate the pipes and pumps from the walls and floors with resilient materials or hangers to break the vibration channel. Also, the pump operation was limited to only one time within any 30 min in the nighttime period. Finally, the noise level inside the unit was found to meet the statutory requirement.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.