Abstract

The mechanical properties of the toroidal field model coil (TFMC) tested as a single coil by current ramping up to 80 kA were analysed. For low ramping rates the displacement transducers and strain gauges gave stable signals. The global coil deformation and stress levels were in good agreement to FEM predictions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.