Abstract

Post-arc current and voltage measurements with high time resolution were carried out with industrial vacuum circuit breakers for investigating their current zero conditions and current interruption. Based on experimental results, plasma parameters were estimated by means of a modified "continuous transition model." Dielectric effects in the post-arc current zero region were detected and modeled. At lower current amplitudes (I/spl circ/<16 kA), typical post-arc currents were obtained. At higher current amplitudes, the probability of higher post-arc current charges increases without the occurrence of breakdowns. It has been shown that charge generation takes place in the post-arc current region.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.