Abstract

A composite tuned mass damper(CTMD) is a vibration control device consisting of an active-passive tuned mass dampers supported on the primary vibrating structure. The performance of CTMD in mitigating wind-induced vibration of tall building is investigated. Optimum parameters of a passive tuned mass damper(PTMD)for minimizing the variance response of the damped primary structure under random loads, with different mass ratio of an active tuned mass damper(ATMD) to a PTMD have been used for the optimum parameters of CTMD. The active control force generated by ATMD actuator was estimated by using linear quadratic Gaussian(LQG) controller, and the fluctuating along-wind load, treated as a stationary random process ,was simulated numerically using the along-wind load spectrum proposed by Solari .Comparing the along-wind rms response of tall building without a CTMD, the CTMD is effective in reducing the response to 40%~45% of the response without the CTMD. Therefore, the CTMD system was effective in reducing wind-induced vibration of tall building.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.