Abstract
AbstractThis study investigates the low‐frequency oscillations (LFOs) in MMC‐MVDC systems with high photovoltaic (PV) penetration, considering the whole operating conditions of the grid‐connected MMC, including both the inverter and rectifier modes. First, the multi‐port impedance models of converters and networks are developed, upon which a stability criterion is defined. The mechanism of LFOs is then identified using bus participation analysis and parameter sensitivity analysis. In addition, the stable zones of the dominant parameters are identified, taking into account the whole operating conditions of the grid‐connected MMC. Interestingly, a phase‐locked loop may induce LFOs in two low‐frequency ranges. Finally, the experimental results confirm the correctness of the theoretical analysis.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.