Abstract
The performance of a 13 kWp roof mounted, grid connected photovoltaic system in Northern Ireland over a period of three years has been analysed on hourly, daily and monthly bases. The derived parameters included reference yield, array yield, final yield, array capture losses, system losses, PV and inverter efficiencies and performance ratio. The effects of insolation and inverter operation on the system performance were investigated. The monthly average daily PV, system and inverter efficiencies varied from 4.5% to 9.2%, 3.6% to 7.8% and 50% to 87%, respectively. The annual average PV, system and inverter efficiencies were 7.6%, 6.4% and 75%, respectively. The monthly average daily DC and AC performance ratios ranged from 0.35 to 0.74 and 0.29 to 0.66, respectively. The annual average monthly AC performance ratios for the three years were 0.60, 0.61 and 0.62, respectively. The performance of this system is compared with that of other representative systems internationally.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.