Abstract
In some power systems, the voltage waveform contains frequency components less than fundamental, called subharmonics or subsynchronous interharmonics. Voltage subharmonics can be both positive- and negative-sequence, independent of their frequency (order). Subharmonics exert harmful effects on sundry electrical equipment, especially on rotating machinery; they cause various noxious phenomena, such as a local saturation of the magnetic circuit, increases in power losses and windings temperature, and torque pulsations leading to vibration of unacceptable severity. Notably, previous works reported excessive vibration of rotating machinery only under no-load, while under full load, rather moderate vibration occurred. This study deals with vibration analysis of a line-start permanent magnet synchronous motor (LSPMSM) supplied with the voltage containing negative-sentence subharmonics. Experimental investigations were conducted for a 3 kW, four-pole production LSPMSM for subharmonics of various values and frequencies. Voltage subharmonics of values significantly less than reported in real power systems were found to cause unacceptable vibration, especially under full load.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.