Abstract
Wide area monitoring system (WAMS) installed in Croatian Transmission system operator (HOPS) control center collects and process synchrophasor data in real time. There are ongoing activities on continuous, incremental and gradual upgrading of existing WAMS with new protection functions and control algorithms towards WAMPAC system. This paper describes line differential protection based on synchrophasor data and implemented on PDC server running in control room. In the first phase, the algorithm was applied to historical synchrophasor data. That check revealed that estimation block in PMUs at both line ends must implement the same estimation technique. Because of this finding, only lines with the same PMU type on both ends were selected for real-time performance test in the second phase. Several months long performance test successfully confirmed a soundness of concept and its implementation. It was proven in practice that new algorithm can be used as an effective tool for validation of basic protection performance and a solid foundation for development and implementation of backup protection.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.