Abstract

Several Trials for Protection and Control Schemes based on the International Electrotechnical Commission (IEC) 61850 standard were recently implemented for the new electrical system at a U.S. oil refinery. IEC 61850, generic object-oriented substation event (GOOSE) messaging, was used for several schemes, including transfer tripping, breaker failure, islanding detection, remote synchronizing, automatic restoration, manual transfer, and load shedding. Site acceptance tests validated the operation of the protection and control schemes. Bench testing was also performed for the load-shedding scheme using a power-system simulator. All of the testing focused on verifying scheme operations during normal operation and failure modes. The experience gained during early project trials influenced the design and testing of subsequent schemes. This article describes the bench and site acceptance testing approaches used and presents example tests along with their relevant results and the lessons learned.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.