Abstract

This paper describes Krško experience and problems that had to be resolved with RTD Bypass Elimination project (RTDBE). Following RTD bypass manifold isolation valve leak in 2008, Krško decided to perform RTDBE modification on reactor coolant system narrow range temperature measurement system. The installation was performed during Outage 2013. Soon after the plant returned to power, newly configured measurement channels showed that OPΔT reactor trip was oversensitive to spikes caused by auxiliary relay operation in the cabinets nearby. The solution was to reconfigure OPΔT trip filtering constants to filter out short-term spikes in the signal. After almost full operating cycle of trouble-free operation, RTD failures started occurring on reactor coolant system cold leg, which was caused by the high frequency vibrations (3-5 kHz) induced by reactor coolant pumps. To resolve RTD failures, Krško ordered re-design of the RTDs to add robustness and specific qualification in high-frequency vibration operating environment. Improved RTDs were installed in Outage 2016 and were operating one full cycle with minor deviations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.