Abstract

This paper proposes a novel fault-ride through method for offshore wind farms connected to grid through a voltage source converter (VSC)-based high voltage direct current (HVDC) transmission. The proposed method introduces a controlled voltage drop at offshore grid when an onshore fault occurs. The idea behind is to achieve a fast power reduction. Additionally in the proposed idea, every individual wind turbine detects the voltage drop of offshore grid almost simultaneously, then its controller decreases the power set-point to reduce the power output from each wind turbine. The effectiveness of this method is verified by numerical simulations performed in PSCAD.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.