Abstract
The study was focused on investigating the spray and droplet characteristics of spiral and flat-fan nozzles computationally. The Spiral nozzle and the flat-fan nozzle are generally used in fire suppression application. The computational analysis had been carried out in ANSYS. The nozzle parameters like spray pattern, spray flow rate, impact, weber number were examined at different pressures say 1 bar to 3 bar. During this study the volume fraction of air and water were maintained equally. The spray pattern of spiral nozzle is not uniform and the droplets produced from the spray are coarse. The flat-fan nozzle produces a solid-cone pattern spray with oval impact area with a width of approximately ½ of its length. The flat-fan nozzle has higher spray flow rates and higher sprays impact than the spiral nozzles. The spiral nozzle acquires the maximum spray angle and the minimum droplet size and hence it is considered as highly efficient spray nozzle.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Vehicle Structures and Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.