Abstract

An epidemiologic investigation was conducted in response to a case of Legionella pneumonia in a scientist working at a federal research facility. A survey of 80 individuals working at the facility revealed that 13 (16%) had sustained prior infections with Legionella pneumophila serogroup 1 (Lps1) as measured by anti-Lps1 antibodies. Antibody-positive individuals' offices clustered around an air cooling tower and a heating, ventilation, and air conditioner unit (odds ratio = 5). On multivariate logistic regression analysis, individuals of non-white race (adjusted odds ratio = 8) and smokers (adjusted odds ratio = 36) were also found to be at higher risk of past infection. Marked Legionella growth was noted in the cooling tower's water reservoir and potable hot water system, where suboptimal operating temperatures were noted. Subsequent increase in the hot water temperatures as well as a complete renovation of the affected building's air handling and potable water systems led to a reduction in Legionella species colonization.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.