Abstract

AbstractIt has been hypothesized that four parameters are solely responsible for a material's performance in a flammability scenario. This excludes effects of material physical integrity, i.e. melting, delamination, etc. They are (1) the critical heat flux below which piloted ignition cannot occur (CHF), (2) the ratio of heat of combustion to heat of gasification (HRP), (3) the thermal response parameter related to the thermal inertia and the ignition temperature (TRP), and (4) the available energy per unit area (AEP). The fire scenario controls the process by its initial heat flux and region of ignition. The hypothesis is applied to 54 tests of the ISO Room Corner Test to assess its validity. It is shown that these four parameters give good correlations in predicting the time to flashover and whether it occurs. In principle, different correlations could be developed for other scenarios of tests and fire configurations. Copyright © 2009 John Wiley & Sons, Ltd.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.