Abstract

We propose a method for the fault passage indication of earth faults in resonant-earthed networks, based on phase current measurements alone. This is particularly relevant for electricity distribution systems at medium-voltage levels. The method is based on the relative magnitudes of the phasor changes in the phase currents due to the fault. It is tested for various network types and operation configurations by simulating the network in pscad and using the simulated currents as the input for an implementation of the method in matlab. In over-compensated networks, the method shows reliable detection of the fault passage, with good selectivity and sensitivity for both homogeneous and mixed (cable and overhead line) feeders. However, for the less common under-compensated systems, it has limitations that are described further in this study. The method has good potential for being cost effective since it requires only current measurements, from a single location, at a moderate sampling rate.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.