Abstract

An LPG filling station incident in Korea has been studied. The direct cause of the incident was concluded to be faulty joining of the couplings of the hoses during the butane unloading process from a tank lorry into an underground storage tank. The faulty connection of a hose to the tank lorry resulted in a massive leak of gas followed by catastrophic explosions. The leaking source was verified by calculating the amount of released LPG and by analyzing captured photos recorded by the television news service. Two BLEVEs were also studied.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.