Abstract

ABSTRACTSpace cooling is a significant energy consumer in office buildings in the subtropical climate zone. An adequate energy policy for indoor spaces should accordingly incorporate both energy conservation and an acceptable level of indoor environmental quality (IEQ). This study investigates the cooling energy consumption for IEQ acceptance in Hong Kong offices adopted for four space-cooling strategies: the ventilation strategies of conventional constant air volume (CAV) systems with a fixed fresh air flow rate; demand-controlled ventilation (DCV) by indoor CO2 concentration; adaptive comfort temperature (ACT) set-point adjustment; and a combination of DCV and ACT operations. Numerical equations and multiple regression formulae were used to evaluate the cooling energy consumption and IEQ acceptance in the target offices, respectively. The results show that systems equipped with DCV are more energy efficient than conventional CAV systems, while a temperature set-point adjusted between 22°C and 23°C shoul...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.