Abstract

Synchronous machines with brushless excitation have the disadvantage that the field winding is not accessible for the de-excitation of the machine. This means that, despite the proper operation of the protection system, the slow de-excitation time constant may produce severe damage in the event of an internal short circuit. A high-speed de-excitation system for these machines was developed, and this study presents the continuation of a previously published study. This study presents the design by computer simulation and the results of the first commissioning of this de-excitation system in a commercial 20 MVA hydro-generator. The de-excitation is achieved by inserting resistance in the field circuit, obtaining a dynamic response similar to that achieved in machines with static excitation. In this case, a non-linear discharge resistor was used, making the dynamic response even better.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.