Abstract

The paper presents the results of measurements and calculations concerning the influence of weather conditions on the operation of wet cooling towers of 905 MWe units of the Opole Power Plant (Poland). The research concerned the influence of temperature and relative humidity of air, wind and power unit load on the water temperature at the outlet from the cooling tower, the level of water cooling, cooling efficiency and cooling water losses. In the cooling water loss, the evaporation loss stream and the drift loss stream were distinguished. In the analyzed operating conditions of the power unit, for example, an increase in Tamb air by 5 °C (from 20–22 °C to 25–27 °C) causes an increase in temperature at the outlet of the cooling tower by 3–4 °C. The influence of air temperature and humidity on the level of water cooling ΔTw and cooling efficiency ε were also found. In the case of ΔTw, the effect is in the order of 0.1–0.2 °C and results from the change in cooling water temperature and the heat exchange in the condenser. The ε value is influenced by air temperature and humidity, which determine the wet bulb temperature value. Within the range of power changes of the unit from 400 to 900 MWe, the evaporated water stream m˙ev, depending on the environmental conditions, increases from 400–600 tons/h to the value of 1000–1400 tons/h. It was determined that in the case of the average power of the unit at the level of 576.6 MWe, the average values of the evaporation and drift streams were respectively 0.78% and 0.15% of the cooling water stream. Using statistical methods, it was found that the influence of wind on the level of water cooling, cooling efficiency and cooling water losses was statistically significant.

Highlights

  • Operation of condenser cooling systems of power unit thermal turbines has a significant impact on the efficiency of electricity generation

  • Water losses in cooling towers are the basic item in the water balance of thermal power units

  • The effects of weather conditions and cooling water parameters on cooling efficiency and water losses are taken into account [7,8,9]

Read more

Summary

Introduction

Operation of condenser cooling systems of power unit thermal turbines has a significant impact on the efficiency of electricity generation.

Results
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.