Abstract

The impact of heterogeneity in soil thermal properties on the performance of horizontal ground heat exchangers (HGHE) is closely examined using a custom-made finite element model. Ensembles of heterogeneous soil fields were generated with spatial correlation parameters derived from similar studies of heterogeneity in hydraulic parameters. Within these soil fields, a single loop HGHE was modelled as discrete pipes placed in a heterogeneous soil continuum. The effect of heterogeneity was found to be minimal relative to uncertainty of the mean soil thermal conductivity, supporting the continued use of the assumption of homogeneity when modelling and designing these systems. Multiple design techniques were identified which would allow HGHE designers to further mitigate any deleterious effects, such as preferential heat transfer between adjacent pipes which may act as a ‘short-circuit’ mechanism, reducing HGHE effectiveness.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.