Abstract

We described here the results of measuring the PCB levels in eleven hundred transformer oil samples using an immunoassay screening method. Five hundred samples out of the total were remeasured using a GPC/GC/ECD method. A comparison of these results on ROC (receiver operating characteristic) plots showed that the immunoassay provides a useful screening method. In the case that the regulatory concentration of the total PCB was set at 0.5 mg/kg, the most suitable cutoff concentration for the immunoassay for screening was calculated to be at 0.4 mg/kg with false negative and false positive rates of zero and seven percent, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.