Abstract

A method for designing a supplemental subsynchronous damping control (SSDC) for an HVDC transmission system is described. The SSDC eliminates torsional instabilities caused by interaction between conventional HVDC controls and turbine-generator rotor torsional modes of vibration. Results of digital simulation used in the design process are compared with measurements made on an HVDC simulator. Results of both digital simulations and HVDC simulator tests which demonstrate SSDC performance are shown. This research and development effort was sponsored by EPRI under RP1425-1.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.