Abstract

Two identical rectangular heat-exchanger fin-arrays, with their bases in the same vertical plane, arranged in series one above the other, were used instead of a single array of double the original length fins to dissipate heat from a vertical rectangular base, which was kept at 40°C above the ambient environment. The effect of the magnitude of the gap width between the two consecutive arrays, upon the steady-state rate of heat transfer from the heated base of the exchanger under natural-convection conditions, was investigated experimentally. When a gap width of 18 ± 2 mm is used, a saving in fin material ensues together with a slight (∼ 3%) increase in the rate of heat dissipation, being achieved.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.