Abstract

A novel methodology is proposed to calculate how much air displacement and contaminant leakage might occur during a power outage that may result in a momentary positive pressure reversal in a BSL-3 facility. Note that the ultimate goal in design and operation of a BSL-3 facility is to achieve sustained directional airflow such that under failure conditions the airflow will not be reversed. The proposed methodology should be applied when and only when all other measures to achieve zero tolerance have been ruled out. Only after determining that zero tolerance cannot be achieved for the BSL-3 facility in question should the model be employed to perform a health and safety risk assessment to determine the reverse airflow tolerance. The methodology is applicable to other room types, such as airborne infection isolation rooms, that use sustained differential air pressure as one means to prevent particle migration across a boundary.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.