Abstract

Arc motion in low voltage (240 VAC) high current (10/sup 3/-10/sup 4/ A) current limiting circuit breakers is dominated by arc root mobility. This is strongly affected by the gas flow and gas composition in the contact region, but there is little experimental data on these effects. New pressure and spectral data measurement during arc movement are presented using a flexible test apparatus and an arc imaging system. These measurements are used to investigate gas flow characteristics in the arc chamber. The chemical and physical phenomena occurring during the arc motion are discussed. The combination of optical and spectral data provides new insight into the arc motion. Also studied are the influences of arc chamber material, contact material, and contact opening speed. These data are used to improve arc control for a low contact opening velocity of 1 ms/sup -1/.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.