Abstract
A “Vapor Chamber” is used as a novel heat spreader to cool high-performance MPUs (micro-processor units). The vapor chamber is placed between small heat sources and a large heat sink. This paper describes the effect of heat source size on the heat transfer characteristics of the vapor chamber. First, by the experiments, the effect of heat source size on the temperature distribution of the vapor chamber is investigated, and the validity of the mathematical model of the vapor chamber is confirmed. Secondly, by the numerical analyses, the effect of heat source size on the thermal resistances inside the vapor chamber is discussed. It is found that the heat source size greatly affects the thermal resistance of the evaporator section inside the vapor chamber. Although the thermal resistance is hardly affected by the heat generation rate and the heat flux of the heat source, it increases as the heat source becomes smaller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series B
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.