Abstract

Flow maldistribution in cross-flow heat exchangers used for industrial air heaters or recuperators is fairly common and can lead to a number of undesirable effects, one of which is deterioration in the thermal performance. The effect of gross flow maldistribution and the improvement in the thermal performance of flow correction guide vanes is investigated using a laboratory heat exchanger apparatus. The thermal performance deterioration from maldistribution was up to around 30 %. Modest improvements in the overall heat transfer coefficient and heat exchanger effectiveness when vanes were used was found for the range of air-side Reynolds numbers tested. Vanes were found to reduce the deterioration in thermal performance by up to 60 % compared to a perfectly uniform flow situation. Based on the e-NTU correlations the thermal performance deterioration is predicted to decrease as the number of tube rows (i.e. NTU) increases. The effective heat transfer area and therefore thermal performance of industrial air heaters and recuperators can be improved by using flow correction devices, such as guide vanes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.