Abstract
Abstract An experimental study of flow boiling of binary organic solution was conducted in a horizontal tube. An organic mixture of miscible fluids, chlorodifluoromethane (R22)–dimethylacetamide (DMAC) was circulated through the experimental system. The influence of the heat source, flow rate, solution concentration and operating pressure on the flow characteristics and the heat transfer coefficient was examined experimentally. Based on the experimental observation an appropriate flow pattern map was constructed. The experimental values of the heat transfer coefficient (HTC) were compared with predicted HTC obtained by several known correlations. Based on these comparisons the well know Dittus & Boelter correlation deviated up to 30%. A better agreement (up to 15%) was obtained by modified the Kattan et al. [10] , [11] , [12] correlation. The modification includes using the Forster and Zuber correlation [21] for nucleate boiling HTC and multiplying the predicted HTC by a constant of 1.4.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.