Abstract
The electrogeometric model (EGM) proposed by Armstrong and Whitehead has been used to calculate the lightning shielding features of transmission lines. While the striking distance equation in the EGM uses the 50% flashover voltage characteristics of negative switching impulses for rod-rod gaps, those characteristics for long air gaps have not been sufficiently examined. The present study has therefore focused on clarifying the 50% flashover characteristics of negative switching impulses for long air gaps. Consequently, saturating characteristics have been obtained for rod-plane gaps compared with almost linear characteristics for rod-rod and rod-conductor gaps. Furthermore, new knowledge was obtained indicating that, for air gaps of around 4 to 5 m, the 50% flashover voltage may possibly be lower for rod-plane gaps than for rod- rod and rod-conductor gaps.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.