Abstract

In order to study the thermal stress of the GIS shell under normal internal pressure in the sunshine environment, First, the 24-hour temperature field on the surface of the GIS shell of a substation is detected for and the temperature change curve is plotted. Then the ANSYS software is used to carry out finite element stress analysis including temperature field on GIS shell. During the analysis, select the highest temperature and lowest temperature periods, fit the temperature distribution curve of the cross section of the shell varying with the angle under the two conditions, and apply the corresponding temperature load of the two conditions to obtain the stress distribution and stress amplitude distribution. The results show that under normal sunlight environment, the stress of the shell without stress concentration is less than 30Mpa, and the stress variation value caused by diurnal temperature difference in most areas of the shell is within 5MPa, and it can reach about 10Mpa at the top where the stress concentration occurs. This study analyzes the stress distribution and fluctuation range of the GIS shell under the solar radiation, which provides important data support for the safety evaluation of the GIS shell.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.