Abstract

The objective of this research is to present an investigation the thermal resistance of ten vapor chambers with different configuration structures with different working fluid fill ratios. The coolant flows entering the cooling section of the vapor chamber with constant mass flow rate of 0.05 kg/s. The de-ionize water is charged into the vapor space under vacuum condition with the ranging of 20–45% by volume. A 125 kW/m2 constant heat flux is applied at the 40 × 40 mm2 heat source area. It can be seen from experiments that the optimized fill ratio to obtain the minimum thermal resistance of the vapor chamber depends on the operating power, geometries and material types of heat sinks, configuration structures inside the vapor chamber. The results obtained from this study are expected to lead to guidelines that will allow designing vapor chamber with the optimized fill ratio to obtain minimum thermal resistance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.