Abstract
The preliminary planning necessary to estimate the amount of current to be interrupted on a large network for staged tests under short-circuit conditions is outlined, also the precautions necessary to keep the applied fault from developing into a total system interruption. The circuit breakers under test are identified, various quantities required for record, and the means of obtaining the same are discussed. The results of a number of tests are given as well as a general discussion as to the conditions of the tests and of results obtained.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.