Abstract

Long EHV ac lines cannot be loaded to its thermal limit to keep sufficient margin against transient instability. EHV lines may be loaded to a very high value if the conductors are allowed to carry superimposed dc current along with ac current. The added dc power flow does not cause any transient instability. In HVDC line the capacitive VAR of the line cannot be tapped to compensate a part of the lagging VAR consumed by the converters. Present paper studies the feasibility of converting a double circuit ac line for simultaneous ac-dc power flow to get the advantages of parallel ac-dc transmission to improve stability and damping oscillations as well as for independent control of ac and dc power transmission. No alterations of conductors, insulator strings and towers of the original line are needed. Substantial gain in the loadability of the line is obtained. Unlike HVDC line, capacitive VAR of the line is available to compensate a part of the lagging VAR.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.