Abstract

Protective current transformers (CTs) are integrated into electrical power systems for assessment of the health of the system. They are intended to provide a scaled-down value of the line current. During major faults, excessive fault currents with decaying DC components could flow through the primary of the CT, causing core saturation and a consequent malfunction of the protection system. This problem is addressed in the paper, and a signal-processing scheme is proposed for fast predetermination of the peak value of the steady-state AC component, instant of occurrence of fault and the time constant of the decaying direct current. Samples of the CT secondary current are collected until the onset of saturation, and are operated upon using a covariance-Prony algorithm to estimate the aforementioned critical parameters. Simulation results in support of the proposed technique are also presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.