Abstract

The subject of this study was a distribution substation that feeds 14 fast DC chargers (80 kW) located at the bus depot in Lublin, Poland. The voltage variations were determined to be within the PN-EN 50160 standard limit values (±10% Un). There were several events registered when 4th, 6th, 8th, and 10th voltage harmonics were above the PN-EN 50160 limit during the charging of the electric buses. The obtained maximum 10 min average values of the total voltage harmonic distortion (THD) were 3.36%, 2.27%, and 2.89% for the first, second, and third phase, respectively, i.e., below the limit value of 8% required by PN-EN 50160. Due to the exceedance of the 6th voltage harmonic, the PN-EN 50160 requirements were not met.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.