Abstract

This study is about determining air gap, insulation material in pipes between 50 mm and 1000 mm in mechanical installation, and determining optimum insulation thickness, energy saving and payback period in cases where both are being used. For this calculation, life cycle cost analysis containing heating degree day has been used. Even though Afyon province climate conditions have been used as the case study, the study has been expanded for cold, temperate and warm climate conditions. This made it possible to make comparative assessments for insulation thickness, air gap, pipe diameter and heating degree day values. In 50 mm and 1000 mm pipes using air gap, the optimum insulation thickness was reduced by 81% and 39% respectively. It is recommended to use air gap in mild climates and to use insulation in cold climates. When insulation with air gap is applied, optimum insulation thickness is reduced, and in pipes with greater diameter energy cost saving is increased while in pipes with smaller diameter the payback period is reduced.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.