Abstract

Power cable diagnosis using isothermal relaxation current (IRC) method has been carried out on the under-grounded XLPE cables, and the results were compared with high voltage DC leakage current (HVDC) method, residual charge measuring (RCM) method. The results of IRC method were correspond with the other method's results generally, and the estimated breakdown voltage calculated from the IRC method was equivalent with actual breakdown voltage. IRC method seems to be comparable to RCM method in accuracy. IRC method is more advantageous diagnosis method to run safely, quickly and economically. It is an economical way since cable system owners can attempt by themselves without giving stress to their cables.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.